| Besides the LON DALI-Controllers the SVEA "REG-S" family of products comprises 4 input/output modules. The modules come with 4 respectively 8 outputs and the same number of inputs.
LON I/O-Module REG-S 4W 4DI 24V 4 relay outputs, changeover contacts (10 A), 4 inputs 24 V
LON I/O-Module REG-S 4W 4S 8DI 24V 4 relay outputs, changeover contacts (10 A), 4 relay outputs, NO contacts (10 A), 8 inputs 24V
LON I/O-Module REG-S MSE2 4DI 24V 4 relay outputs (10 A) for 2 drive units, 4 inputs 24 V
LON I/O-Module REG-S MSE4 8DI 24V 8 relay outputs (10 A) for 4 drive units, 8 inputs 24 V
Characteristics:
Status LED for every input and output
Manual operation for every input and output
Pluggable screw-type terminals
Supply voltage: AC 230 V
Free Topology Transceiver (FTT)
Configurable reaction of the outputs to power-down/power-up/bus reset
Usually, conventional pushbuttons are connected to the digital inputs to operate the consumer loads at the outputs. Apart from that, the digital inputs can be used for floating contacts, e.g. of motion detectors, photoelectric lighting controllers or thermostats, independently of the outputs. The contact current is approx. 10 mA. The contact voltage of about 24 V is generated by the device itself, so that no external power supply unit is required. Every input status as well as the output states are indicated by one status LED each. By pushbuttons on the casing top, every output can be operated manually.
The state of each input and output are indicated with a status LEDs. The buttons on the front of the device allow a manual operation of each output. The common device state is indicated via the service and run-LED. The service button is located well accessible on the front of the module.
All cables can be connected to the device using pluggable screw-type terminals. The REG-S modules are some of the few LON actuators that provide the opportunity to configure the outputs' reaction to power-down as well as to power-up/reset.
Included in delivery are standardised and powerful application programs according to the LonMark guidelines. Furthermore the modules can be configured comfortably by the help of a LNS-Plug-In. |